Pile Cloth Media Filtration
Severn Trent - Little Aston STW
Scope of services
- Design
- Manufacture
- Installation
- Commission
Scope of delivery
- 2 x Mecana SF 12/60 Unit - Standard Cloth
- 3 x Mecana SF 6/30 Unit - Microfibre Cloth
- 2 x Flocculation Tank
- 5 x Local Control Panels
- All associated pipework >DN400 & valves
- GMS Access Steelwork
Specifics
- Grade 304 stainless steel
- SF 12/60: 120 sqr. metres of Standard cloth
- SF 6/30: 90 sqr. metres of Microfibre cloth
Technical data
- Design Horizon 2028
- Effluent P Consent @ 0.2 mg/l
- Influent FFT @ 16,312 cubic metres/day (188 l/s)
- Population Equivalent: 25,112
Client
MMB for Severn Trent
Completion
September 2019